Serie WH45P

Overview

Fire dampers Series WH45P ensure maximum safety in the prevention of the spread of fires within the buildings. Indeed they guarantee the perfect heat insulation and complete seal is to hot to cold smoke fumes as demonstrated by the numerous tests performed according to standard EN 1366-2.
Fire dampers WH45P series are characterized by the highest performance, up to EI 180 S, and particularly for the possibility of installation method "Wechschott" into large openings with sealing in high density rock wool and coating with endothermic coat.

By connecting the dampers to the fire alarm system and smoke detectors can anticipate the closing of the blade compared to the direct action of the flame and thus preventing the onset of indirect damage arising from the spread of smoke and gases generated by combustion.

Technical data

  • Sizes from Ø200mm to Ø800mm
  • Classified for installation:
    • within the walls filled with concrete or cellular concrete or masonry 100 mm minimum thickness 500 Kg/m³ minimum density class EI 120 (ve i↔o) S ;
    • within the walls filled with concrete or cellular concrete or masonry 150 mm minimum thickness 500 Kg/m³ minimum density class EI 180 (ve i↔o) S ;
    • within concrete floors 150 mm minimum thickness 2200 Kg/m³ minimum density class EI 180 (ho i↔o) S;
    • within concrete floors 150 mm minimum thickness 650 Kg/m³ minimum density class EI 120 (ho i↔o) S;
    • within concrete floors 100 mm minimum thickness 650 Kg/m³ minimum density class EI 90 (ho i↔o) S;
    • lightweight plasterboard walls by a minimum thickness of 100 mm class EI 120 (ve i↔o) S
    • in solid plaster stud partition walls with a minimum thickness of 70 mm class EI 90 (ve i↔o) S
    • in solid plaster stud partition walls with a minimum thickness of 100 mm class EI 120 (ve i↔o) S
  • Fire behavior:
    • automatic closure to reach the temperature of 70 ° C in less than 30 seconds
    • insulation to heat and flame
    • no thermal bridge between the faces of the wall installation
    • absence of thermal bridge between the channels upstream and downstream
    • any source of fire
  • Reaction to smoking:
    • damper function in the absence of fire and smoke (cold smoke) and during the fire (hot smoke) tested to 500Pa
  • Case tightness:
    • class B minimum in accordance with EN 1751 for all the sizes
  • Corrosive environments
    • salt spray exposure test performed in accordance with EN 60068-2-52 overcome with degree of severity 2.
  • Controls: mechanical, magnetic or motorized
  • Thermofusible calibrated at 70 ° C or 95 ° C, certified by VDS Germany
  • Safety lock adapted to ensure the maintenance of the closure of the damper even in the case in which the fire completely destroy the closing command
  • Absence of a preferential direction for the flow of air
  • Air velocity up to 15m/s
  • Duct in galvanized carbon steel